HVAC — capture filter loading and volume flow mechanically
02Fig. · HVAC and Air ConditioningRixen Industrie-Lösung

Industry / HVAC and Air Conditioning

HVAC — capture filter loading and volume flow mechanically

Filters age, dampers drift, volume flows shift. A ring balance delivers the current differential pressure over weeks, months, and years — no drift, no readjustment required, directly usable for replacement intervals, volume flow control, and filter diagnostics.

A

Typical installation points

  • Before and after filter stages (G4, F7, F9, HEPA H13/H14)
  • Across dampers and volume flow controllers
  • Between supply and exhaust ducts
  • In stairwells for smoke-control overpressure (pressure ventilation)
  • In control cabinets to monitor filter mats

B

Why a ring balance fits here

HVAC is less about peak accuracy and more about long-term stability. An electronic pressure sensor in a ventilation duct is stressed by vibration, temperature swings, and humidity — drift, zero-point shift, and sensor failures follow. The ring balance is a passive mechanical measuring element: no diaphragm or spring under pressure load, no components that age or fatigue.

Filter monitoring
When pressure drop rises above a threshold, a contact switches or the 4–20 mA signal triggers a filter-change alarm.
Volume flow measurement
Combined with an orifice plate, a ring balance converts differential pressure directly into a volume flow display — square-root scale available on request.
Stairwell overpressure
Intrinsically safe variant (RW65_EX_II) for combustible environments, ATEX-certified.
Long-term stability
No drift from vibration or temperature cycles — the measuring element does not age.
Steady signal at small spans
In the typical filter monitoring range (50–250 Pa) the mechanical inertia of the ring body acts as a low-pass filter — pressure fluctuations from fan start-up or duct turbulence are physically damped. No nervous output signal, no damping parameters in the controller that can be misconfigured. At larger spans (>600 Pa) the restoring force of the calibration weight dominates and response time shortens accordingly.

C

Technical parameters

Typical spans
0–100 Pa, 0–250 Pa, 0–600 Pa, 0–1,800 Pa
Accuracy
±1.5 % FS or ±1.5 Pa
Signal output
4–20 mA, 0–10 V, switching contacts
Protection
IP54 / IP65 depending on variant
Operating temperature
−10 to +50 °C
Media compatibility
Resistant to aggressive gases and dirty air

Trusted by

In building technology, Rixen instruments are trusted by: SIEMENS AG, Honeywell, ABB, Johnson Controls, Wacker Chemie.

Your project

Volume-flow scale or filter alarm contact to your specification. Typical lead time two to four weeks ex works.