Draft measurement and furnace pressure control
03Fig. · Furnace and Thermal ProcessRixen Industrie-Lösung

Industry / Furnace and Thermal Process

Draft measurement and furnace pressure control

Industrial furnaces, combustion chambers, and thermal process plants depend on stable draft — typically −20 to −300 Pa negative pressure. Aggressive flue gases, high temperatures at the connection, and continuous load are the challenge. A ring balance measures here without electronic sensors in the medium and on request delivers the control signal for damper actuation directly.

A

Typical applications

  • Draft measurement in industrial-furnace flue ducts
  • Furnace pressure control with three-point step controllers
  • Differential pressure across heat exchangers and filter assemblies in combustion
  • Monitoring of glass melting tanks and smelting furnaces
  • Combustion plants and boilers in power generation

B

Why a ring balance fits here

In flue gas with condensates, acid traces, and dust, conventional differential pressure sensors would fail within a short time. The ring balance has an encapsulated measuring element that only contacts the medium through highly flexible pressure connections. The housing sits at a safe distance. Cleaning and purge connections are possible.

Robustness
Brass measuring element, corrosion-resistant against typical flue-gas components
Maintenance-free
No springs that drift from burner vibration
Long-term stability
Units from the 1980s still run on grandfathering — replacement available from the appliance number
Integrated control
Rixotact 4 has a three-point step controller built in, directly driving the throttle damper
Mechanical low-pass filter
Industrial furnaces are dynamic processes — dampers, burners, and load changes cause the differential pressure to constantly shift in level. The rotational inertia of the ring body physically dampens short-term pressure spikes: no software filter required, no parameterisation, no additional failure source.
Trends at a glance
The analogue scale shows oscillations and pressure tendencies immediately — on-site personnel can tell without any software whether the furnace is running stably, whether a damper is misadjusted, or whether the draft is gradually deteriorating.

C

Technical parameters

Typical spans
0 to −300 Pa, ±100 Pa, 0 to −1,000 Pa
Accuracy
±1.5 % FS or ±1.5 Pa
Sealing liquid
Mineral oil (≤ ±700 Pa) or Galden® (up to ±2.1 kPa)
Measuring element material
Brass
Housing
Polycarbonate / fibreglass

Trusted by

In furnace construction and combustion technology, Rixen instruments are trusted by: Saint-Gobain, Johnson Controls, Bakker & Co., Innovatherm, Supratec. A note from the records: a furnace pressure regulator "Rixotact" built in 1985 was returned for inspection in 2019 — and was within tolerance per the calibration report. That is the result of 34 years of continuous operation in an industrial furnace.