Products / Differential pressure gauges

Differential Pressure Gauges for Low Pressure — from 40 Pa

A differential pressure gauge shows the difference between two pressures — between a cleanroom and an airlock, upstream and downstream of a filter, or a furnace chamber against ambient. All Rixen instruments are differential pressure gauges based on the ring balance principle: spans from 40 Pa to 1,800 Pa, measured mechanically, without a spring and without drift. Max. error: ±1.5 % FS (> 100 Pa) or ±1.5 Pa (< 100 Pa).

Why a ring balance instead of a diaphragm or capsule?

Diaphragm, capsule and Bourdon tube gauges measure via the deformation of an elastic element. At pressures of a few pascals, that element is the weak point. The ring balance measures differently:

01

Weight force, not a spring

The pressure difference rotates a pivoted ring body against the weight force of a calibration weight until equilibrium is reached. The rotation angle is the measure of the differential pressure.

02

No drift

Without an elastic element, nothing in the measuring path ages. Electronic sensors have documented drift of 0.2 to 1 % FS per year — the ring balance physically does not.

03

Steady reading

At small spans the sealing liquid acts as a mechanical low-pass filter: pressure spikes and turbulence are damped, and the pointer stays steady.

Measuring principle in detail

The models

All instruments use the same ring balance measuring element with the same accuracy. They differ in whether and how the reading is passed on.

Differential pressure gauge MU-Analog-65
Most widely used

MU-Analog-65

Analogue scale + 4–20 mA

150×150 mm scale plus three outputs as standard: 4–20 mA, 0–20 mA and 0–10 V for BMS and SCADA. The scale remains readable during a power outage.

View product
Differential pressure gauge MU-Digital
Most widely used

MU-Digital

LCD + 4–20 mA

3½-digit LCD and the same three outputs. The standard transmitter for cleanrooms, ventilation and HVAC.

View product
Differential pressure gauge RW65

RW65

Pure indicator

Analogue 150×150 mm scale, no electronics, no power supply. Optionally with up to two switching contacts (MK or NAMUR IK).

View product
Differential pressure gauge RW65_EX_II

RW65_EX_II

Intrinsically safe (ATEX)

For Zones 0/1/2 and 20/21/22 (II 1 GD Ex ia IIC/IIIC T4 Ga Da). Scale readable without power, plus a passive 4–20 mA output.

View product

Comparison

MU-Analog-65 MU-Digital RW65 RW65_EX_II
DisplayAnalogue scale 150×150 mmLCD, 3½-digitAnalogue scale 150×150 mmAnalogue scale 150×150 mm
Outputs4–20 mA · 0–20 mA · 0–10 V4–20 mA · 0–20 mA · 0–10 Vnone (optionally up to 2 switching contacts)4–20 mA passive (2-wire)
Supply24 VAC · 110 VAC · 230 VAC · 24 VDC24 VAC · 110 VAC · 230 VAC · 24 VDCnone required11–30 V DC via Zener barrier / isolating amplifier
ProtectionIP65IP54IP65IP65 (steel) · IP66 (stainless steel)
ATEXnononoII 1 GD Ex ia IIC/IIIC T4 Ga Da

For all instruments: measuring ranges as any combination between ±20 Pa and ±1,800 Pa (smallest span 40 Pa), max. error ±1.5 % FS (> 100 Pa) or ±1.5 Pa (< 100 Pa), selectable display unit (Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C.), connection via 8 mm hose nozzles.

Which differential pressure gauge fits?

Should the reading go to a BMS, SCADA or PLC?

Yes → MU-Analog-65 (with analogue scale) or MU-Digital (with LCD). No → RW65.

Must the display remain readable during a power outage?

Yes → MU-Analog-65, RW65 or RW65_EX_II. The LCD of the MU-Digital needs power.

Is the measurement in a hazardous area?

Yes → RW65_EX_II. The other instruments have no ATEX approval.

Is a limit switching contact required?

RW65 with up to two MK or NAMUR IK contacts; in hazardous areas the RW65_EX_II with up to two NAMUR contacts.

Further instruments and accessories

MU-Analog-65-2L

Like the MU-Analog-65, but as a passive 2-wire transmitter: loop-powered via the 4–20 mA line, no separate power supply.

View product

Rixotact 4

Differential pressure controller with 0–10 V output and three-point step controller — for furnace pressure control and active room pressure control.

View product

Room pressure probe RDS

Mechanical wall feed-through for room pressure tapping, tool-free installation, compatible with all Rixen instruments.

View product

Frequently asked questions

Which differential pressure gauge do you need?

Measuring range, display, signal output, Ex zone — tell us the key data of your application and we will recommend the right instrument.

Note: The content of this page is provided for general guidance and replaces neither the operator's risk assessment nor case-by-case verification by qualified personnel. Responsibility for sizing, equipment selection, installation and operation lies solely with the operator. Despite careful preparation, we accept no liability for accuracy or completeness; the currently valid edition of the applicable regulations and standards prevails.