Products / Differential pressure gauges
A differential pressure gauge shows the difference between two pressures — between a cleanroom and an airlock, upstream and downstream of a filter, or a furnace chamber against ambient. All Rixen instruments are differential pressure gauges based on the ring balance principle: spans from 40 Pa to 1,800 Pa, measured mechanically, without a spring and without drift. Max. error: ±1.5 % FS (> 100 Pa) or ±1.5 Pa (< 100 Pa).
Diaphragm, capsule and Bourdon tube gauges measure via the deformation of an elastic element. At pressures of a few pascals, that element is the weak point. The ring balance measures differently:
01
The pressure difference rotates a pivoted ring body against the weight force of a calibration weight until equilibrium is reached. The rotation angle is the measure of the differential pressure.
02
Without an elastic element, nothing in the measuring path ages. Electronic sensors have documented drift of 0.2 to 1 % FS per year — the ring balance physically does not.
03
At small spans the sealing liquid acts as a mechanical low-pass filter: pressure spikes and turbulence are damped, and the pointer stays steady.
All instruments use the same ring balance measuring element with the same accuracy. They differ in whether and how the reading is passed on.

Analogue scale + 4–20 mA
150×150 mm scale plus three outputs as standard: 4–20 mA, 0–20 mA and 0–10 V for BMS and SCADA. The scale remains readable during a power outage.
View product
LCD + 4–20 mA
3½-digit LCD and the same three outputs. The standard transmitter for cleanrooms, ventilation and HVAC.
View product
Pure indicator
Analogue 150×150 mm scale, no electronics, no power supply. Optionally with up to two switching contacts (MK or NAMUR IK).
View product
Intrinsically safe (ATEX)
For Zones 0/1/2 and 20/21/22 (II 1 GD Ex ia IIC/IIIC T4 Ga Da). Scale readable without power, plus a passive 4–20 mA output.
View product| MU-Analog-65 | MU-Digital | RW65 | RW65_EX_II | |
|---|---|---|---|---|
| Display | Analogue scale 150×150 mm | LCD, 3½-digit | Analogue scale 150×150 mm | Analogue scale 150×150 mm |
| Outputs | 4–20 mA · 0–20 mA · 0–10 V | 4–20 mA · 0–20 mA · 0–10 V | none (optionally up to 2 switching contacts) | 4–20 mA passive (2-wire) |
| Supply | 24 VAC · 110 VAC · 230 VAC · 24 VDC | 24 VAC · 110 VAC · 230 VAC · 24 VDC | none required | 11–30 V DC via Zener barrier / isolating amplifier |
| Protection | IP65 | IP54 | IP65 | IP65 (steel) · IP66 (stainless steel) |
| ATEX | no | no | no | II 1 GD Ex ia IIC/IIIC T4 Ga Da |
For all instruments: measuring ranges as any combination between ±20 Pa and ±1,800 Pa (smallest span 40 Pa), max. error ±1.5 % FS (> 100 Pa) or ±1.5 Pa (< 100 Pa), selectable display unit (Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C.), connection via 8 mm hose nozzles.
Yes → MU-Analog-65 (with analogue scale) or MU-Digital (with LCD). No → RW65.
Yes → MU-Analog-65, RW65 or RW65_EX_II. The LCD of the MU-Digital needs power.
Yes → RW65_EX_II. The other instruments have no ATEX approval.
RW65 with up to two MK or NAMUR IK contacts; in hazardous areas the RW65_EX_II with up to two NAMUR contacts.
Like the MU-Analog-65, but as a passive 2-wire transmitter: loop-powered via the 4–20 mA line, no separate power supply.
View productDifferential pressure controller with 0–10 V output and three-point step controller — for furnace pressure control and active room pressure control.
View productMechanical wall feed-through for room pressure tapping, tool-free installation, compatible with all Rixen instruments.
View productMeasuring range, display, signal output, Ex zone — tell us the key data of your application and we will recommend the right instrument.
Note: The content of this page is provided for general guidance and replaces neither the operator's risk assessment nor case-by-case verification by qualified personnel. Responsibility for sizing, equipment selection, installation and operation lies solely with the operator. Despite careful preparation, we accept no liability for accuracy or completeness; the currently valid edition of the applicable regulations and standards prevails.