Differential Pressure Transmitter – MU-Digital

Ringbalance Differential Pressure Transmitter converts draft, pressure and differential pressure into standard signals of 0-20mA, 4-20mA and 0-10V.

Description

Ringbalance Differential Pressure Transmitter converts draft, pressure and differential pressure into standard signals of 0-20mA, 4-20mA and 0-10V.

 

– Display LCD, 3 1/2 digit, 12.5 mm high

– Measuring System Ringbalance principle

– Measuring Pickup Magnetic “Hall” sensor

– Measuring Ranges freely selectable from 0…40 Pa (+/-20 Pa) to 0…1.8 kPa

– Units Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C.

– Ambient Temp. 0 . . . +50 °C (32 – 122 °F)

– Accuracy max. error +/-1.5% of span, or +/-1.5 Pa

– Housing for wall mounting IP42; Polycarbonate lightgrey;

– Process Connect. 2 fittings for flexible tubes, 8mm outside diameter

– Electr. Connections screw terminals in the terminal box

– 2 cable fittings PG9/M16 with strain relief

– Electrical Outputs 0-20 mA, 4-20 mA and 0-10 V;

– Max. Loads 680 Ohm (mA); respectively: min. 2kOhm (V)

– Power Supply 230 VAC; or 24/110/120/240/24 VAC;
24 V DC (additional charge)

– CE Electromagnetic Compatibility according to

– EN50081-2 (Emmission) and EN50082-2

Additional information

Gehäuse IP-Schutzart

IP42